APC Smart-UPS SRT 2200VA 230V and APC Smart-UPS SRT 72V 2.2kVA Battery Pack
Jump to navigation
Jump to search
- 1 x APC Smart-UPS™ SRT 2200VA 120V (SRT2200XLA)
- 1 x APC Smart-UPS™ SRT 72V 2.2kVA Battery Pack (SRT72BP)
- 2 x APC Smart-UPS™ On-Line Tower to Rack-Mount Conversion Rail Kit (SRTRK4)
- 1 x APC MasterSwitch Plus (AP9225) - Rackmount PDU with network management
- MasterSwitch Rack PDU
- Load Capacity: 1440 VA
- Output Voltage: 120V
- Outlets: (8) NEMA 5-15R
- Input Voltage: 120V
- Input Plug Type: NEMA 5-15P
- Cord Length: 15 ft
- Dimensions: 1.88″x 19″x 6.5″
- Weight: 7 LBS.
- Default credentials: apc/apc
- AP9225 Manual
- Serial cable: UPS Communications Cable Smart Signalling (940-0024 or 940-1524 -- schematic here)
- Serial port mode: 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.
- 1 x APC MasterSwitch Plus Expansion Unit (AP9225EXP) - Rackmount PDU with serial port to connect to the APC MasterSwitch Plus
- Setup:
- Software: apcupsd <http://www.apcupsd.org/> running on my Minnowboard Max providing network-level access to UPS status
- Minnowboard Max USB port -> UPS RJ45 serial port ( cable: APC 940-0127A + a serial-to-USB adapter )
- /etc/apcups/apcupsd.conf
# The most important lines: UPSNAME SRT2200 UPSCABLE smart UPSTYPE modbus DEVICE /dev/ttyUSB1 # The rest: LOCKFILE /var/lock SCRIPTDIR /etc/apcupsd PWRFAILDIR /etc/apcupsd NOLOGINDIR /etc ONBATTERYDELAY 6 BATTERYLEVEL 5 MINUTES 3 TIMEOUT 0 ANNOY 300 ANNOYDELAY 60 NOLOGON disable KILLDELAY 0 NETSERVER on NISIP 0.0.0.0 NISPORT 3551 EVENTSFILE /var/log/apcupsd.events EVENTSFILEMAX 10 UPSCLASS standalone UPSMODE disable STATTIME 10 STATFILE /var/log/apcupsd.status LOGSTATS off DATATIME 0
- apcupsd running on all devices on the network / using the UPS power
root@minnowmax # apcaccess APC : 001,039,0917 DATE : 2023-06-21 16:14:24 -0400 HOSTNAME : pve1 VERSION : 3.14.14 (31 May 2016) debian UPSNAME : APC UPS CABLE : Custom Cable Smart DRIVER : MODBUS UPS Driver UPSMODE : Stand Alone STARTTIME: 2023-06-21 16:01:57 -0400 MODEL : Smart-UPS SRT 2200 STATUS : ONLINE LINEV : 120.8 Volts LOADPCT : 9.9 Percent LOADAPNT : 10.6 Percent BCHARGE : 100.0 Percent TIMELEFT : 220.0 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds OUTPUTV : 119.9 Volts DWAKE : 0 Seconds DSHUTD : 0 Seconds ITEMP : 26.0 C BATTV : 82.1 Volts LINEFREQ : 60.1 Hz OUTCURNT : 2.16 Amps NUMXFERS : 0 TONBATT : 0 Seconds CUMONBATT: 0 Seconds XOFFBATT : N/A SELFTEST : NO STATFLAG : 0x05000008 MANDATE : 2020-08-30 SERIALNO : AS203XXXXXXX BATTDATE : 2000-01-02 NOMOUTV : 120 Volts NOMPOWER : 1804 Watts NOMAPNT : 2200 VA FIRMWARE : UPS 06.0 / 00.5 END APC : 2023-06-21 16:14:31 -0400